Fixed power analyzer

CVM-B50-ITF

CVM-B50-ITF, Power analyzer 96 x 96

Code: M56910.COMING SOON

  • Protocol: Modbus TCP/IP
  • Memory: Yes
  • Communications: Ethernet | Wi-Fi
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 4
  • Measuring Channels: 4
  • Harmonics: 31
  • Input current: .../5 A | .../1 A
  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

The CVM-B50 is a panel-mounted power analyzer (96 × 96 mm) with energy logging, downloadable memory, and integrated web server. It allows start-up via the app or web server without additional software and features an automatic wiring error correction system for simple installation.

Ideal for analysing electrical variables and consumption quality, including voltage and current THD%, as well as individual phase harmonics up to the 31st order. Neutral current measurement enables detection of imbalances and potential neutral conductor overloads.

Compact and versatile, it performs four-quadrant measurements (consumption and generation), suitable for both Medium and Low Voltage installations.

Characteristics of the device

  • 40 days of built-in downloadable memory in CSV (mobile or PC)
  • Configuration, display and start-up via app or web server
  • Neutral current measurement
  • THDU%, THDI%, and harmonics (up to 31st order)
  • Automatic Autowiring system (wiring error correction)
  • Wi-Fi and Ethernet communications (Modbus TCP/IP)
  • 4 inputs, 2 relay outputs, and 2 digital outputs
  • User-defined screen creation with selected variables
  • Display of active quadrant and power usage percentage
  • Current measurement via .../5 A, .../1 A, .../250 mA or flexible clamps (depending on model)
  • On-screen indication of the status of outputs, inputs and/or active tariff.

Applications

The CVM-B50 is specially designed to analyse changes in electrical variables, detect network harmonics, and measure energy, facilitating energy audits in accordance with ISO 50001 or obtaining CAE certification in the Spanish market.

Neutral current measurement allows the detection of circulating currents that may cause issues in the installation. The device can be integrated into SCADA systems for remote management and monitoring via Wi‑Fi or wired Ethernet connection.

It features digital inputs for logging consumption from other meters via pulses, detecting the status of installation sensors, or distinguishing consumption by tariff. Additionally, the digital outputs allow automation of the installation through open/close commands based on any measured instantaneous value.

SPECIFICATIONS

Mechanical characteristics
Weight (kg)
0,363
Envelope
Self-extinguishing V0 plastic
Fastening
Panel
Size (mm) width x height x depth
96 x 96 x 67 (mm)
AC power supply
Nominal voltage
100 ... 240 V ~ ± 10%
Frequency
50 ... 60 Hz
Consumption
5 ... 8 VA
Installation category
CAT III 300 V
DC power supply
Nominal voltage
100 … 240 Vcc ± 10%
Consumption
2.7 ... 3 W
Installation category
CAT III 300 V
Voltage measurement circuit
Nominal voltage
230V F-N, 400 V F-F
Frequency measuring range
50 ... 60 Hz
Input impedance
400 kΩ
Minimum measurement voltage (Vstart)
11,5 V F-N
Maximum value
300 VF-N /520 VF-F
Installation category
CAT III 300 V
Current measurement circuit
Nominal current (In)
5A - .../5A , .../1 A
Minimum current measurement
10 mA
Installation category
CAT III 300 V
Measurement accuracy
Phase voltage measurement
0.2% (20 ... 120% Un)
Phase current measurement
0.2% (10% In ≤ I ≤ 120%In)
Active power measurement (kW)
0.5% ± 2 digit
Apparent power measurement (kVA)
0.5% ± 2 digit
Reactive power measurement (kvar)
1% ± 2 digit
Digital transistor outputs
Quantity
2
Type
NPN
Maximum voltage
24 Vdc
Maximum current
50 mA
Maximum frequency
16 imp / s
Pulse width
30 ms a 400 ms (Programmable)
Digital relay outputs
Electrical life (at maximum load)
60x103 cycles
Mechanical life
10x106 cycles
Maximum switching capacity
625 VA / 75 W (AC1)
Digital inputs
Quantity
4
Type
NPN
Input/output insulation
2000 V
User interface
Display type
LCD Custom COG
LED
2 LED
Keyboard
3 keys
Environmental characteristics
Operating temperature
-10 …+50 ºC
Storage temperature
-25...+75 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP 20, Front IP54
Standards
Standards
IEC/EN 61010-1; IEC/EN 61010-2-030; IEC 613626-1; UNE-EN 55016-2-1; UNE-EN 61000-4-2; UNE-EN 61000-4-20; UNE-EN 61000-4-4; UNE-EN 61000-4-5; UNE-EN 61000-4-6; UNE-EN 61000-4-8; UNE-EN IEC 61000-4-11; UNE-EN 61000-4-3; UNE-EN 60068-2-1; UNE-EN 60068-2-2; UNE-EN 60068-2-78; ETSI-EN 301 489-1 Ver. 2.2.3; ETSI-EN 301 489-17 Ver. 3.3.1; EN-18031-1; IEC 61557-12
Electrical safety, Installation category
CAT III 300 V

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Technical guide
3D
Dimensions
Diagram connection
Datasheet
CE-certified
Software & Firmware

ACCESORIES