Current transformers narrow section, flat strip 3x100x10 mm

TC12 2500/5A

TC12 2500/5A, Current transformers narrow section

Code: M70386.CONSULTAR DISPONIBILIDAD

  • Flat strip(mm): 100 x 50
  • System: Single-phase
  • Class 0,5 Power (VA): 20
  • Class 1 Power (VA): 30
  • Class 3 Power (VA): 40
  • Measurement Range (A): 2500/5
  • Input current: 2500 A
  • Transformer type: Closed core

INFORMATION

Description

  • Type: bar entrance
  • Types: from 40 to 4000 A
  • Internal diameter: from 20.3 to 63 mm, depending on the type
  • Busbar dimensions: from 25 x 5 mm to 30 x 100 mm
  • Individual certificate available on request
  • DIN rail fixing accessory (Types TC5 and TC6)
  • Secondary coding types .../5 A (on demand .../1 A. TC4 not available)

Applications

Converting a high nominal current to a lower current so that it can be measured by the unit. In installations where the electrical supply can be interrupted to install transformers.

SPECIFICATIONS

Mechanical characteristics
Weight (kg)
0,8
Envelope
Plastic wrap V0 self-extinguishing, UL 94
Size (mm) width x height x depth
129 x 155 x 78 (mm)
Electrical characteristics
Safety factor (SF)
FS 5
Power
30 VA (Class 1)
Current measurement circuit
Primary current measurement
2500 A
Transformation ratio
… / 5 A
Nominal frequency
50 / 60 Hz
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ max.
Environmental characteristics
Thermal Class
Class B (+130 ºC)
Relative humidity (without condensation)
15 … 95 %
Protection class
IP 20
Standards
Standards
IEC 61869-1, IEC 61869-2, BS2627