Current transformers narrow section, flat strip 20x10 mm

TC5 75/5A

TC5 75/5A, Current transformers narrow section

Code: M70314.DISCONTINUED

  • Flat strip(mm): 20 x 10 |25 x 5 |15 x 5
  • System: Single-phase
  • Class 1 Power (VA): 2
  • Class 3 Power (VA): 3,5
  • Measurement Range (A): 75/5
  • Input current: 75 A
  • Transformer type: Closed core

INFORMATION

Description

  • Type: bar entrance
  • Types: from 40 to 4000 A
  • Internal diameter: from 20.3 to 63 mm, depending on the type
  • Busbar dimensions: from 25 x 5 mm to 30 x 100 mm
  • Individual certificate available on request
  • DIN rail fixing accessory (Types TC5 and TC6)
  • Secondary coding types .../5 A (on demand .../1 A. TC4 not available)

Applications

Converting a high nominal current to a lower current so that it can be measured by the unit. In installations where the electrical supply can be interrupted to install transformers.

SPECIFICATIONS

Mechanical characteristics
Weight (kg)
0,298
Envelope
Plastic wrap V0 self-extinguishing, UL 94
Fastening
DIN rail with accessory
Size (mm) width x height x depth
58 x 77 x 59 (mm)
Electrical characteristics
Safety factor (SF)
FS 5
Power
2 VA (Class 1)
Current measurement circuit
Primary current measurement
75 A
Transformation ratio
… / 5 A
Nominal frequency
50 / 60 Hz
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ max.
Inner diameter Ø (mm)
20,3
Environmental characteristics
Thermal Class
Class B (+130 ºC)
Relative humidity (without condensation)
15 … 95 %
Protection class
IP 20
Standards
Standards
IEC 61869-1, IEC 61869-2, BS2627

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

3D
Dimensions
Datasheet
CE-certified

ACCESORIES



TAMBIÉN TE PUEDE INTERESAR