Filtre actiu multinivell

AFQm-3WP-070C-690

AFQm-3WP-070C-690, Filtre actiu multifunció

Code: R7JF6P.PROPERAMENT

  • Sistema de mesura: 3 fils, 400...690 V
  • Corrent de fase (A): 70
  • Corrent de cresta (A): 140
  • Fixació: En sòl

INFORMACIÓ

Descripció

The floor mounted AFQm multilevel active filters are the most complete solution for solving power quality problems in three-phase industrial, commercial or service installations caused by the presence of harmonics and the consumption of reactive power. These following characteristics and functions have been implemented in the cabinet type active filters:

  • Filtering capacity per module of 100 A (400 ... 480 Vac) and 70 A (550 ... 690 Vac), capacity per cabinet between 100 ... 400 A (400 ... 480 Vac) and 70 ... 280 A (550. .. 690 Vac).
  • Cabinets expandable with small-sized rack modules.
  • Range for installations with 3 wires (3W model to 690 Vac) or 4 wires (4W model to 550 Vac).
  • Multi-range voltage and dual frequency (50/60 Hz).
  • Reduction of harmonic currents up to the fiftieth harmonic (2,500 Hz)
  • Selection of harmonic frequencies to be filtered for maximum filter effectiveness.
  • Power factor correction both inductive and capacitive .
  • Phase current balancing, improvement of consumption in neutral (4W model).
  • If higher filtering capabilities are required, the system can be expanded using AFQm racks connected in parallel (all filters/racks must be of the same 3- or 4-wire model).

Aplicacions

Solució ideal per a instal·lacions, amb gran quantitat de càrregues monofàsiques i trifàsiques que siguin generadores d'harmònics com ara ordinadors, SAI, lluminàries, aparells elevadors, aires condicionats amb variador, etc. També per a instal·lacions que requereixen una bona qualitat de subministrament amb vista a augmentar l'eficiència de la producció oa millorar la continuïtat de subministrament del sistema.

ESPECIFICACIONS

Mechanical characteristics
Weight (kg)
192
Noise
< 70 dBA
Connection type
Network: M8 ring terminal, Ground: M10 ring terminal, Current: 6-pole connector, RS-485: 3-pole connector, Ethernet: RJ-45
Size (mm) width x height x depth
608 x 1890 x 812 (mm)
AC power supply
Nominal voltage
208 … 550 V~ F-F (± 10 %)
Frequency
50 / 60 Hz (± 5 %)
Installation category
4 kV, CAT III Class 1
Electrical characteristics
Maximum phase current
70 A (RMS)
Current crest factor
2:1
Rated peak current Ipk
84 kA
Conditional short-circuit current (Icc)
40 kA
Rated diversity factor (RDF), simultaneity
1
Característiques elèctriques
Sistema de terres
TN, TT
Current measurement circuit
Transformation ratio
5 … 5000 / 5A
Measurement accuracy
Voltage harmonics (THD)
25 % (max)
Power supply output
Power
83650 VA
Comunicació sèrie
Tecnologia / Tipus
RS-485
Protocol
Modbus/RTU
Comunicacions xarxa
Tecnologia / Interfície
Ethernet
Comunicació xarxa
Protocol
TCP/IP, Modbus TCP
User interface
Display type
TFT color, 3.5" touchscreen
Environmental characteristics
Operating temperature
-10 ... +45 ºC
Storage temperature
-20 ... +50 ºC
Relative humidity (without condensation)
0 ... 95 %
Protection class
IP 21 (IP 41 on demand) / IK10
Features / performance
Filtering / Response time
2º … 50º harmonic (selectable) / < 100 µs
Phase compensation
Selectable
Reactive power compensation (Kvar)
Selectable
Priority scheduling
Selectable
Parallel assembly/installation
Up to 100 devices of different caliber. Connection of transformers only in Master unit.
Standards
Electrical safety, Maximum height (m)
5000

DIMENSIÓ

CONEXIÓ

VÍDEOS

DESCÀRREGUES

Dimensions
Diagram connection
User's manual
Datasheet
Video Installation
Catàleg
Díptic